WEBs LAB
LAB 2 WEB AX Station Software Installation & Registration.............3 LAB 3 Niagara Workbench Overview...................................................9
1. Open Platform 打开Platform....................................................................................9 2. Start a Station 运行一个站点.....................................................................................9 3. View the Demo 浏览演示站点...............................................................................10 4. Stop a Station 停止一个站点...................................................................................11 LAB 4 Create a New Station................................................................13 LAB 5 Programming for AHU.............................................................17
LAB 6 Graphics 图形界面..................................................................27
1. Create folders for graphics建立图形文件夹...........................................................27 2. Create a New View of the folder 为文件夹建立图形页面...................................27 3. Switch between View and Edit Mode of Px sheet....................................................29 4. Px sheet in file system and Delete Px sheet..............................................................29 5. Add graphics from WEBsAX library.......................................................................30 6. Link Graphics and points 连接图形和点...............................................................32 7. Import your custom graphics 导入自定义图形...................................................37 8. Add controllable modules from WEBsAX Library..................................................37 9. Advanced Graphic: Panes 高级图形工具............................................................40 10. Link from page to page 连接页面到页面...........................................................41 11. Make Nav File 制作Nav导航文件...................................................................43 12. Use IE view the graphic 使用IE浏览器查看...................................................43
LAB 7 Alarm 报警...............................................................................45
1. Add Alarm Service 添加Alarm报警服务............................................................45 2. Set Alarm Class 设定报警分类...............................................................................45 3. Add Alarm Recipient 添加报警接收处理...............................................................45 4. Add Alarm Extension to the Point 添加报警扩展到点...........................................46 5. Using Alarm Portal...................................................................................................48 6. HyperLink to Alarm Console 连接到报警控制台...................................................50
LAB 8 Schedule 时间表......................................................................51
1. Add Weekly Schedule...............................................................................................51 2. Add Calendar Schedule module to Wire Sheet.........................................................54 3. Add Trigger Schedule module to Wire Sheet...........................................................54 4. HyperLink to Schedule 连接到时间表....................................................................55
LAB 9 History and Dynamic Trend 历史记录和动态趋势...............56
History...............................................................................................................................56 1. Add History Service 添加History历史服务.........................................................56
Honeywell ECC Asia Pacific Technical Assistance Center Page:1/130
2. Add History Extension to the Points 添加历史记录扩展到点................................56 3. Modify the History Extension Property 修改历史记录扩展属性...........................56 4. History Config 配置历史记录................................................................................57 5. View the History 查看历史记录..............................................................................57 6. Manager the History 管理历史记录........................................................................59 7. HyperLink to History 连接到历史纪录...................................................................60 Dynamic Trend.................................................................................................................61 LAB 10 Report /Email 报表和邮件....................................................62 Report Service:..................................................................................................................62 1. Add Report Service 添加Report报表服务...........................................................62 2. Layout report data in a ComponentGrid 设定报表格式..........................................62 3. Create a Px page display of the report 为报表建立一个图形页面.........................64 4. Create and configure ExportSource component.......................................................67 Email Service....................................................................................................................67 1. Add Email Service 添加Email服务......................................................................67 2. Add email account 添加email 帐户........................................................................68 3. Add EmailRecipient to ReportService......................................................................68 4. Add EmailRecipient to AlarmService......................................................................69 LAB 11 Security 安全设定..................................................................71 1. Configure CategoryService......................................................................................71 2. Assign Components to Categories 分配组件到分类目录......................................71 3. Configure User Service 配置用户服务....................................................................72 LAB 12 Commissioning WEBs Controller..........................................74 LAB 13 Use a Spyder as Lon I/O for WEBs........................................84 LAB 14 Link Station to Station............................................................98
LAB 15 Module Library and Reuse 模块库和重复利用.................106
1. Import new modules 导入新的模块.....................................................................106 2. Customize a palette 自定义palette.......................................................................106 3. Reuse Program 重复利用程序.............................................................................107 4. Reuse Graphic 重复利用图形...............................................................................108
LAB 16 Backup 备份........................................................................109
1. Back up the Station 备份工作站............................................................................109 2. Restore the Station还原工作站备份.....................................................................110 3. Histories Archive 历史记录归档...........................................................................112 LAB 17 Spyder Commissioning........................................................117
Honeywell ECC Asia Pacific Technical Assistance Center Page:2/130
LAB 2 WEB AX Station Software Installation & Registration
Objectives:
Get to know the installation and registration process. 了解安装和注册的过程。
Instructions:
1. Confirm PC requirements(确认PC机要求):
Processor: Intel Pentium. IV, 3 GHz or higher.
Operating System: Microsoft Windows. NT 4.0 with ServicePack 4 or higher. Internet Explorer. 5.0 or later, or Netscape Communicator. 4.5 or later.
Hard Drive: 10 GB minimum, 25 GB for applications that need more archiving capacity.
Modem: 56 KB minimum, Full time, high speed ISP connection is recommended for remote site access (for example,TI, ADSL, cable modem).
Display: Video card and monitor capable of displaying 1024 x768 pixel resolution. Network Support: Ethernet adapter (10/100 megabit with RJ-45 connector). Memory: 2 GB minimum
2. Software installation (软件安装)
Follow the installation wizard with local administrator privilege, but note the several steps.
以本地管理员权限按照安装模板安装,但是注意几个步骤
2.1.Install “distribution file” for Webs controller. Check the first option. (安装Webs控制器可用的distribution file,选择第一项)
Honeywell ECC Asia Pacific Technical Assistance Center Page:3/130
2.2.Select the language packages for proper display of local language. 选择本地语言设置包用于本地语言的正确显示
2.3 Install and start Platfom Daemon.(安装并运行Webs-AX后台程序环境)
Honeywell ECC Asia Pacific Technical Assistance Center Page:4/130
3. Check license (检查License状况)
Popup a message window when first run Workbench.(第一次运行Workbench时会跳出提示窗口)
If you don’t connect internet, popup a license view including Host ID and other information needed in registering the software.
如果没有连到Internet,会跳出以下的信息框,包含Host ID和其他的注册软件所需的信息。
If you have internet connection, a web page will show up, you can fill the necessary information then submit for license file.
如果有internet的连接,会跳出注册网页如下,填好必要信息然后发送。
Honeywell ECC Asia Pacific Technical Assistance Center Page:5/130
4 Install license file.(安装许可文件)
Copy and paste the license file to “licenses” folder of program directory. 如果已经取得License文件直接复制到安装路径的”licenses”文件夹里
Honeywell ECC Asia Pacific Technical Assistance Center Page:6/130
5 Review license file (查看许可文件)
5.1. Open Local host Platform with click “Open platform”under “Open” of “File” icon. (点击Open platform 在FileÆ Open菜单下)
5.2. Select local and fill the administrator username and password of Windows
选择Local 并且填入Windows管理员用户名和密码
Honeywell ECC Asia Pacific Technical Assistance Center Page:7/130
5.3. select the License Manager under platform and open the License file. 选择License Manager 并且打开License 文件
Honeywell ECC Asia Pacific Technical Assistance Center Page:8/130
LAB 3 Niagara Workbench Overview
Objective: Go over the Niagara Workbench. Start/Stop a Station. 目标: 熟悉Niagara Workbench界面,启动和停止一个站点。
Instructions / 指导:
1. Open Platform 打开Platform
Open WEBStation (Niagara Workbench 运行WEBStation
File Menu – Open – Open Platform
Host IP: localhost Port 3011(default)
Login with administrator username and password.
File菜单-Open – Open Platform,
Host IP: localhost Port 3011 (default默认) 输入管理员用户名和密码登陆。
2. Start a Station 运行一个站点
Double click “Application Director” in Platform. 双击Platform中的Application Director。
Honeywell ECC Asia Pacific Technical Assistance Center Page:9/130
Select demo in view pane. Click “Start” button to start the “demo” station. 选择站点名为demo的station。点击Start按钮启动站点。
The status of demo station change from “idle” --”Starting”--“Running”. Demo站点的状态由idle 闲置--starting启动中-- Running运行。
3. View the Demo 浏览演示站点
Open Internet Browser. Open address “localhost”. Login with username: ”admin”, password: “” (blank).
打开网页浏览器。打开地址localhost。用户名admin密码空登陆。
Honeywell ECC Asia Pacific Technical Assistance Center Page:10/130
Browse the demo station. 浏览demo站点。
4. Stop a Station 停止一个站点
Double click “Application Director” in Platform. 双击Platform中的Application Director。
Select demo in view pane. Click “Stop” button to stop the “demo” station.
Honeywell ECC Asia Pacific Technical Assistance Center Page:11/130
选择站点名为demo的station。点击Stop按钮停止站点。
Honeywell ECC Asia Pacific Technical Assistance Center Page:12/130
LAB 4 Create a New Station
Objectives:
Get to know how to create a new station in the local PC. (For WEBs controller, we can use Station Commissioning Wizard that will practice in LAB12)
了解如何在本地PC上创建新的Station.
Instructions:
1. Open the New station wizard.
Click the “new station” under “Tools” menu icon. 点击Tools 菜单下的new station.
2. Name the new station (use yourname+WEBs01 to avoid duplicated ) 给新station命名
Honeywell ECC Asia Pacific Technical Assistance Center Page:13/130
3. Define the other properties. Like password, ports,etc. 定义其他属性,密码,端口
4. New station is built up.
You can view it in the Sys Home tree.(新的Station建立,可在文件树中看到)
Honeywell ECC Asia Pacific Technical Assistance Center Page:14/130
5. Start the new station.(启动这个新的Station)
6. Open the new station.
After new station started up, then open the station. 新的station启动后,打开这个Station.
Honeywell ECC Asia Pacific Technical Assistance Center Page:15/130
Select local and fill the username (default is admin) and password 选择Local和填写密码
7 The station show after opened. (station打开后显示)
Honeywell ECC Asia Pacific Technical Assistance Center Page:16/130
LAB 5 Programming for AHU
Objectives:
From this Lab, we will get to know how program for WEBs controller. Including created control points, build up the control sequences, link the modules and points up and debug the program.
从这个实验里,我们将了解如何给WEBs控制器编程。包括创建control point,建立控制逻辑, 连接点和模块并且调试程序。
Instructions:
1. Add the KitControl into Palette.
Click to open Palette library and select KitControl.
添加KitControl到Palette,点击打开Palette库并选择KitControl.
Honeywell ECC Asia Pacific Technical Assistance Center Page:17/130
2. Create folders for Logic and points.
Create two new folders for AHU logic and Control points. (In this lab, we don’t have a real device connection, these points just for programming simulation. In real engineering, we connect real I/Os to program and may not need these points)Named the new folders “AHULogic” and “AHUPoints”.
建立2个新文件夹分别用于AHU逻辑和点(这个实验中,我们没有实际的设备连接,这些点仅用作程序的仿真,在实际的工程中,我们连接I/O到程序可能并不需要这些代理点),分别命名新的文件夹为”AHULogic”和”AHUPoints”
3 Create the Control points for AHU Control.(建立用于AHU控制的代理点) And edit the properties of these points(并定义这些点的属性)
Name Type Units Precision minmax SupplyAirTemperature NumricWritable Temperature(k),°C 1 0.0 50.0 ReturnAirTemperature NumricWritable Temperature(k),°C 1 0.0 50.0 ReturnAirSetpoint NumricWritable Temperature(k),°C 1 0.0 50.0 CoolingValve NumricWritable Misc(),percent(%) 0 0 100 HeatingValve NumricWritable Misc(),percent(%) 0 0 100 tureText falseText ReturnAirDamper BooleanWritable Open Close OutsideAirDamper BooleanWritable Open Close ExhaustAirDamper BooleanWritable Open Close FilterDPS BooleanWritable Alarm Normal SupplyFanStatus BooleanWritable On Off SupplyFanAlarm BooleanWritable Alarm Normal ReturnFanStatus BooleanWritable On Off ReturnFanAlarm BooleanWritable Alarm Normal SupplyFanSS BooleanWritable On Off Honeywell ECC Asia Pacific Technical Assistance Center Page:18/130
ReturnFanSS BooleanWritable On Off
Writable type is convenient for program simulation, the real inputs isn’t writable. 可写属性便于程序仿真,实际的输入是不可写的。
4 Create an AHU control logic.
Double click the “AHULogic” icon to open “wiring sheet”.
4.1. We assume the AHU control includes 3 items;假设有3个控制要求
• Return air temperature control, PID samples the return air temperature and return air setpoint and output to cooling valve and heating valve. 回风温度采用PID控制,采集回风温度和设定点并控制冷热水阀。
1°C Heating Cooling ValveValve Setpoint
Honeywell ECC Asia Pacific Technical Assistance Center Page:19/130
• Supply fan interlocked with return fan. Supply fan start/stop then return fan start/stop,
送回风机联锁, 送风机启/停则回风机启/停。
• Valves, dampers interlocked with supply fan status. When supply fan is running then the valve start PID output, dampers are ON.
阀门和风阀与送风机状态联锁,当送风机运行PID输出许可,风阀打开。
4.2. Drag modules from Kitcontrol palette and drop them into “AHUlogic” wiring sheet.(从Palette拖放KitControl模块到AHUlogic的wiring sheet)
Drag and drop the following modules(拖放以下的模块) Module type name From Loopoint CoolPID HVAC-KitControl Loopoint HeatPID HVAC-KitControl
Substract HeatSP Math-KitControl
4.3. Display the properties and inputs/outputs of the modules. Right click the module, click the Pin Slots and select the properties or inputs/outputs that need to be displayed.
显示各个模块的属性和输入输出。右击模块点击Pin Slots选择要显示的属性和输入输出。
Honeywell ECC Asia Pacific Technical Assistance Center Page:20/130
Confirm the following slots are displayed. 确认以下的属性或输入输出显示
Loopoint Substract
Out Out Loop Enable In A Controlled Variable In B Setpoint Loop Action
Proportional constant Integral constant Derivative constant
4.4. Edit the properties of modules. 编辑各个模块的属性
Honeywell ECC Asia Pacific Technical Assistance Center Page:21/130
Edit the modules as following requirements. 编辑属性如下面的要求
HeatPID CoolPID HeatSP Loop Action: Reverse Loop Action:Direct In B : not null, 1.00 Proportional constant: 20 Proportional constant: 20 Integral constant: 0 Integral constant:0 Derivative constant: 0 Derivative constant: 0 Others: default Others: default
(Click and expand it)
4.5. Link the inputs/outputs between modules.
Press the relative slots and drag to slots of other modules. 连接各个模块的输入输出。
From To Link1 HeatSP: Out HeatPID: Setpoint Link2 HeatSP: In A CoolPID: Setpoint
Honeywell ECC Asia Pacific Technical Assistance Center Page:22/130
Link3 CoolPID: Loop Enable HeatPID: Loop Enable Link4 CoolPID:Controlled variable HeatPID:Controlled variable
4.6. Reorder the modules. Right click the wiring sheet, select Reorder icon in the popup menu. 给模块排序,右击wiring sheet, 在跳出菜单上选择Reorder。
Reorder the modules as the follow capture picture. 按下列的顺序排列各模块
Honeywell ECC Asia Pacific Technical Assistance Center Page:23/130
4.7. Link points to the modules. 连接模块和点
Mark the point that will be linked. Then right click module and link from the point.
标记要连接的点,然后右击模块连接这个点。
Select the source slot and target slot. 选择源Slot和目的Slot.
Honeywell ECC Asia Pacific Technical Assistance Center Page:24/130
Build up the following links. 建立以下连接
Source Target Link5 ReturnAirSetpoint, Out HeatSP. In A Link6 ReturnAirTemperature. Out CoolPID. Controlled VariableLink7 CoolPID.Out CoolingValve. In10 Link8 HeatPID.Out HeatingValve. In10 Link9 SupplyFanStatus.Out CoolPID.LoopEnable
4.8. Link the interlocked points. 连接联锁的点
The method is similar with the Item 4.7. 方法与4.7类似 Build up the following links.建立以下连接
Source Target Link6 SupplyFanStatus. Out ReturnFanSS.In10 Link7 SupplyFanStatus. Out ReturnAirDamper. In10 Link8 SupplyFanStatus. Out OutsideAirDamper.In10 Link9 SupplyFanStatus. Out ExhaustAirDamper.In10
5 Test the program. 程序测试
Set the test value for points then check the module outputs and other interlock points. 设定点的测试值然后检查模块的输出和其他的联锁点。
Honeywell ECC Asia Pacific Technical Assistance Center Page:25/130
For this simple program, you can test as following tables 对于这个简单程序,可以按照以下的逻辑关系进行测试。
SupplyFanStatus = On ReturnAirSetpoint=25C
ReturnAirTemperature ReturnAirTemperature
=26C =23C
CoolingValve 20% 0% HeatingValve 0% 20% ReturnAirDamper On On OutsideAirDamper On On ExhaustAirDamper On On ReturnFanSS On On
SupplyFanStatus
=OFF
0% 0% Off Off Off
Off
.
Honeywell ECC Asia Pacific Technical Assistance Center Page:26/130
LAB 6 Graphics 图形界面
Objective: This lab will introduce how to build graphics and link with logic, points. When you finished lab, you will have a graphic for the AHU. 目标: 本练习将介绍如何制作图形界面并和程序与点进行链接。
Instructions / 指导:
1. Create folders for graphics建立图形文件夹
Create a SubFolder named “ PxHome” under folder “Config” of Station “WEBs01” used for graphics pages.
在WEBs01 Station中Config目录下新建文件夹“PxHome”,用于存放图形页面。
Create a SubFolder named “ AHU01” under folder “PxHome”, we will put graphics for AHU01 in it.
在PxHome目录下新建文件夹“AHU01”,用于存放空调机AHU01对应图形页面。
2. Create a New View of the folder 为文件夹建立图形页面
Select folder “AHU01” in PxHome, drop down the View Selector and choose “New View” to create Px file.
Honeywell ECC Asia Pacific Technical Assistance Center Page:27/130
选中PxHome中AHU01文件夹,在View Selector选择菜单下拉列表中选择“New View”创建相应Px文件。
In the popup window, input View Name : “AHU01”, Target Media select “Workbench PxMedia”, Source choose “Px File”, and click OK button. The workbench will create a Px page for “AHU01” and switch into the edit mode.
在弹出窗口中, View Names输入“AHU01”,Target Media 选择“Workbench PxMedia”,Source 选择“Px File”,点击“OK”确认,Workbench将创建对“AHU01” 的图形页面,并进入编辑模式。
Honeywell ECC Asia Pacific Technical Assistance Center Page:28/130
3. Switch between View and Edit Mode of Px sheet
切换浏览和编辑模式
Double click “AHU01” in the side bar pane or select “AHU01” in the View Selector, in the view pane will show the view mode of “AHU01” Px sheet.
双击左边面板中的“AHU01”,或者在View Selector 中选择“AHU01”,在view pane工作界面中会显示 “AHU01”的图形显示模式。
Select “Edit AHU01” in the View Selector, workbench will switch to Edit mode of AHU01 Px sheet.
在View Selector中选择“Edit AHU01”,系统将进入“AHU01”的图形编辑模式。
4. Px sheet in file system and Delete Px sheet
图形页面在文件系统中位置,删除图形页面
In the side bar pane, open folder “Files” in Station “WEBs01”, spread “px” folder, you will find a file named “AHU01.px” which is correspond to Px sheet of “AHU01” folder. Using the windows explorer, you can find it in “WEBsAX install folder\\stations\\WEBs01\\px”.
展开在左侧面板中WEBs01站点“Files”文件夹,展开“px”文件夹,你会发现一个名称为“AHU01.px”的文件,其对应了“AHU01”文件夹的Px Sheet图形页面。 如果你使用windows自带的资源管理器也可以在WEBsAX安装目\\ stations\\WEBs01\\px下找到该文件。
Honeywell ECC Asia Pacific Technical Assistance Center Page:29/130
Delete Px Sheet: Double click AHU01 in PxHome, select “Slot Sheet” in View
Selector. Select the row which name is “AHU01”, right click on it, and delete. Px Sheet in folder AHU01 is deleted. The file “AHU01.px” in “File\\px” will not be deleted at this time.
删除 Px Sheet: 双击PxHome中的AHU01文件夹,在View Selector中选择“Slot Sheet”,选择名称为“AHU01”的行,右键Delete删除,此时文件夹
AHU01对应的图形页面被删除了。而存放在File\\px中的”AHU01.px”文件并未被删除。
Create a Px View for AHU01 again. You will find the popup window as below.
Choose “Overwrite” at this time.
按前述方法重新为AHU01建立图形页面。你会发现如下弹出窗口,请选择“Overwrite”。
5. Add graphics from WEBsAX library
从WEBsAX库中添加图形
Switch to the Edit mode of AHU01 px sheet.
Honeywell ECC Asia Pacific Technical Assistance Center Page:30/130
Select the Canvas (background), modify the View Size to 1024*768 in Properties Pane. (This size should based on the site resolution.)
切换到AHU01的图形页面编辑模式。
选择桌布(背景),在属性Properties面板中修改可视尺寸为1024*768。(尺寸的大小应根据实际站点分辨率调整)
Open “KitPxHvac” in Palette.
Drag and drop “ductA” in folder “ducts” into the canvas. (If you want to delete, right click on the components and select delete in the menu.)
打开Palette中“KitPxHvac”。
选择ducts文件夹中的ductA组件,拖放到编辑桌面中间。(如果你需要删除,在组件上右键,菜单中选择delete删除。)
Honeywell ECC Asia Pacific Technical Assistance Center Page:31/130
6. Link Graphics and points 连接图形和点
BooleanImage
Open “KitPx” in Palette. Add a “BooleanImage” into the canvas.
打开Palette中“KitPx”面板。添加一个“BooleanImage”组件到工作区域。
Double click the “BooleanImage” component in canvas. In the pop up the
properties window, click “…” button to modify “Image” property.
双击工作区中的“BooleanImage”组件。弹出属性窗口,点击“…”按钮修改“Image”属性。
Honeywell ECC Asia Pacific Technical Assistance Center Page:32/130
Modify the True Value. In File Chooser find My modules/kitPxHvac/Dampers
修改True Value。在File Chooser中选择My modules/kitPxHvac/Dampers
Honeywell ECC Asia Pacific Technical Assistance Center Page:33/130
Modify the False Value, and finish as below. Click OK to save.
修改False Value,完成后如下图。OK保存。
Modify the “Ord” property of “BooleanImage”. In the popup window drop menu choose “Component Chooser”.
修改“BooleanImage”的Ord属性。在弹出窗口下拉框中选择“Component Chooser”。
In “Select Ord” window, find AHUPoints/OutsideAirDamper
在“Select Ord”窗口中选择AHUPoints/OutsideAirDamper
Honeywell ECC Asia Pacific Technical Assistance Center Page:34/130
OK to finish. Modify the “BooleanImage” component size to show the full picture, and drag to a proper place in duct.
OK完成。修改 “BooleanImage”图形组件的大小以全部显示,并拖放到风管的合适位置。
Bound Label
Open “KitPx” in Palette. Add a “BoundLabel” to the canvas.
Modify the Ord property of the “BoundLabel” component in canvas as below.
Honeywell ECC Asia Pacific Technical Assistance Center Page:35/130
OK to finish. And the value of the cooling valve will show, drag it to property place.
打开Palette中“KitPx”面板。添加一个 “BoundLabel”组件到工作区。 修改其Ord 属性如下图所示。OK完成。冷水阀Cooling Valve值显示,拖放到合适位置。
KitPxHvac
Open “KitPxHvac” in Palette. Add a equipment\\“fanRight” to the canvas. Modify the Ord property of the “fanRight” component in canvas as below. OK to finish. And the fan picture will show on the canvas, drag it to property place.
打开Palette中“KitPxHvac”面板。添加一个equipment中“fanRight”组件到工作区。 修改其Ord 属性如下图所示。OK完成。风机图片显示,拖放到合适位置。
Honeywell ECC Asia Pacific Technical Assistance Center Page:36/130
7. Import your custom graphics 导入自定义图形
Create your own .jpg format file by Paint. Copy the file to the WEBsAX install folder\\stations\\WEBs01\\px.
Find it in Side Bar Pane: Station(WEBs01)\\Files\\px. If it is not showed, right click on the tree select Refresh Tree Node.
Drag the file on to the AHU01 Px sheet in Edit mode. (note:the image can not be re-scaled)
建立你自己的.jpg格式文件(可使用画图板)。把该文件复制到WEBsAX安装目录\\WEBs01\\px下。
在左侧面板中:Station(WEBs01)\\Files\\px找到该文件,如果没有显示,则在树形结构上右键选择Refresh Tree Node刷新。
在编辑模式下,选中并拖放这个文件到AHU01的图形界面上。(注意:图片文件不能缩放。)
8. Add controllable modules from WEBsAX Library
从WEBsAX库中添加可控制图形模块
Open “KitPx” in Palette. Add a “SetPointSlider” to the canvas.
Modify the Ord property of the “SetPointSlider” component in canvas as below. OK to finish. A slider bar show on the canvas.
Honeywell ECC Asia Pacific Technical Assistance Center Page:37/130
打开Palette中“KitPx”面板。添加一个 “SetPointSlider”组件到工作区。 修改其Ord 属性如下图所示。OK完成,拉动条在图形上显示。
Drag and drop the point “ReturnAirSetpoint” in AHUPoints into the canvas. In the pop up window, check “Make Display Name Lable”. OK to finish.
选择并拖动AHUPoints中的点“ReturnAirSetpoint”到工作区。 弹出如下窗口。选择“Make Display Name Lable”,OK完成。
Switch to View mode to see the result. 切换到查看模式观察结果。
Honeywell ECC Asia Pacific Technical Assistance Center Page:38/130
Using the components in “kitPx”;”kitPxHvac” to finish the graphic as below. 使用“kitPx”;”kitPxHvac”中的组件,完成如下图图形界面。
Boolean Image true image: module://kitPxHvac/dampers/damperH5.gif false image: module://kitPxHvac/dampers/damperH1.gif
ord: station:|slot:/AHUPoints/ReturnAirDamper
Boolean Image true image: module://kitPxHvac/coils/filterV5.gif false image: module://kitPxHvac/coils/filterV1.gif
ord: station:|slot:/AHUPoints/FilterDPS
Image: module://kitPxHvac/coils/coolingCoilv2wLTrue.gif
Image: module://kitPxHvac/coils/heatingCoilv2wLTrue.gif
Honeywell ECC Asia Pacific Technical Assistance Center Page:39/130
Image: module://kitPxHvac/devices/tempSensorTop.gif
Boolean Image
true image: module://kitPxHvac/equipment/fanLeftTrue.gif false image: module://kitPxHvac/equipment/fanLeftFalse.gif ord: station:|slot:/AHUPoints/ReturnFanStatus
9. Advanced Graphic: Panes 高级图形工具
Create a folder named “Panes” under PxHome and create a new view called “Panes” for it. Modify the canvas size.
在PxHome目录下建立一个新的文件夹叫“Panes”,并为其建立一个图形页面名称“Panes”。修改工作区尺寸。
Open “bajaui” in Palette. Add a Panes\\“TabbedPane” to the canvas. Drag and drop a Widgets\\“BoundTable” into the “TabbedPane”;
Drag and drop a Widgets\\“BoundTable” into the “TabbedPane” again.
打开“bajaui”,添加一个Panes 中的“TabbedPane”到桌面工作区。 选择并添加一个Widgets中“BoundTable”到“TabbedPane”上; 再次添加一个Widgets中“BoundTable”到“TabbedPane”上;
Honeywell ECC Asia Pacific Technical Assistance Center Page:40/130
10. Link from page to page 连接页面到页面
Create a New View in folder PxHome called: “Homepage” as a user interface home page.
Change the Background color to what you like in the Properties of Canvas Pane. Open the bajaui Palette; find “HyperlinkLabel” in Widgets folder. Drag it into the canvas.
在PxHome文件夹建立一个新的视图名为“Homepage”,作为用户界面首页。更改背景颜色属性,为你喜欢的颜色。
打开bajaui Palette,在Widgets文件夹中找到“HyperlinkLabel”,拖放到编辑页面中。
Modify the properties of this “HyperlinkLabel”, Text: “Link to AHU01”.
修改这个“HyperlinkLabel”的属性,Text为“Link to AHU01”。
Honeywell ECC Asia Pacific Technical Assistance Center Page:41/130
Modify the Ord properties, drop down the menu and select “Component Chooser”.
修改Ord属性,在弹出窗口中选择“Component Chooser”。
Select Ord: PxHome\\AHU01 (not PxHome\\AHU01\\AHU01). This is to select the Hyperlink target page.
在弹出窗口中找到并选择PxHome\\AHU01。这里选择了链接目标页面。
Honeywell ECC Asia Pacific Technical Assistance Center Page:42/130
Click OK to continue. Switch to View mode and test the link.
Use the same method to add an “Back to Homepage” Hyperlink in AHU01 PxSheet.
点击OK继续。切换到查看模式并测试这个链接。
使用相同的方法在AHU01图形页面中添加“Back to Homepage”返回到主页的连接。
11. Make Nav File 制作Nav导航文件
Right click on Station(WEBs01)\\Files\\px folder. In the new menu select
NavFile.nav and name: MyNavfile.nav.
在Station(WEBs01)\\Files\\px folder文件夹上右键。New新建菜单中选择NavFile.nav,并命名为MyNavfile.nav
Double click the file MyNavfile.nav. Double click the “Home” in the Result Tree. Modify the Target Ord, select folder “PxHome” in component chooser.
双击新建立的MyNavfile.nav文件。在右侧出现的Result Tree窗口中双击Home行。修改Ord属性,在component chooser中选择文件夹”PxHome”。
Press New button in Result Tree window. Enter a new Display Name: AHU01. Target Ord select “AHU01” folder in component chooser. Ok to finish and get result as below:
点击Result Tree窗口中的New按钮。添加一个新的Display Name: AHU01。 Target Ord 选择AHU01文件夹。Ok完成得到如下结果:
12. Use IE view the graphic 使用IE浏览器查看
Open Internet Explore. Type in “localhost”or your IP in URL. 打开IE浏览器。在地址栏输入localhost或IP地址。
Honeywell ECC Asia Pacific Technical Assistance Center Page:43/130
Click Yes, if there is java popup windows. 如果有弹出窗口请选择yes.
After successful login, you will see the user interface is very similar with the Niagara Workbench.
Double click on PxHome\\AHU01 to view the graphic we have done.
在成功登陆后,你可以看见一个和Niagara Workbench非常相近的工作界面。双击PxHome\\AHU01查看刚才做的图形页面。
Honeywell ECC Asia Pacific Technical Assistance Center Page:44/130
LAB 7 Alarm 报警
Objective: Learn how to use alarm service/classs/recipient, alarm console. 目标: 如何使用报警服务,分类,处理,报警控制台。
Instructions / 指导:
1. Add Alarm Service 添加Alarm报警服务
Check whether the “AlarmService” is in the “Config\\Services”.
If not, open the “alarm” module in Palette. Select and drag the “AlarmService” in to the Services of Station(WEBs01).
检查报警服务 “AlarmService”是否在“Config\\Services”中。
如果没有,则打开Palette中的“alarm”模块。选择“AlarmService”并拖动到Station(WEBs01)的Services中。
2. Set Alarm Class 设定报警分类
Double click “AlarmService” to open the WireSheet. There is a “Default Alarm Class” in the wiresheet.
To add another kind of Alarm Class, select “AlarmClass” in alarm Palette, drag it into the wiresheet. Double click the “Alarm Class” component to config the Properties.
双击“AlarmService”打开其WireSheet。 其中有一个默认报警类别”Default Alarm Class” 。
要新增加一个报警类别,选中alarm Palette中的“AlarmClass”,并拖动其到wiresheet中。双击“Alarm Class”组件可以修改其属性。
3. Add Alarm Recipient 添加报警接收处理
Select “ConsoleRecipient” in alarm Palette and drag it into the AlarmService WireSheet.
Honeywell ECC Asia Pacific Technical Assistance Center Page:45/130
Link “ConsoleRecipient”-RouteAlarm to “Default AlarmClass”-Alarm. Then any alarm type of “Default AlarmClass” will report to the “ConsoleRecipient”.
选中alarm Palette中的“ConsoleRecipient”并拖动它到AlarmService的WireSheet中。
连接“ConsoleRecipient”的RouteAlarm到“Default AlarmClass”的Alarm。则所有“Default AlarmClass”类别的报警将报告给Console控制台。
Select “LinePrinterRecipient” in alarm Palette and drag it into the AlarmService WireSheet. Double click this component to modify its property include printer.
Link “LinePrinterRecipient”-RouteAlarm to “AlarmClass”-Alarm. Then any alarm type of “AlarmClass” will be printed.
选中alarm Palette中的“LinePrinterRecipient”并拖动他到AlarmService的WireSheet中。双击该组件配置其属性包括打印机。
连接“LinePrinterRecipient”的RouteAlarm到“AlarmClass”的Alarm。则所有“AlarmClass”类别的报警将被打印。
4. Add Alarm Extension to the Point 添加报警扩展到点
Double click the point “SupplyAirTempature” in AHUPoints to its Property Sheet. Select “OutOfRangeAlarmExt” in alarm Palette Extensions folder, drag it into the end of “SupplyAirTempature” Property Sheet.
双击AHUPoints中的点“SupplyAirTempature”到其属性页面。
在alarm Palette中Extensions文件夹下选择“OutOfRangeAlarmExt”,拖动添加到“SupplyAirTempature”属性页面的末端。
Honeywell ECC Asia Pacific Technical Assistance Center Page:46/130
Expand the OutOfRangeAlarmExt in property sheet. Modify the Alarm Class to “Default Alarm Class”. Modify the Time Delay to 30s
Modify the Alarm Enable, enable toOffnormal and disable toFault. Modify the To Offnormal Text: “SupplyAirTempature Offnormal”
Modify the Hyperlink Ord: select component chooser and find : /PxHome/AHU01 Modify the Offnormal Algorithm Hight Limit 30 Low Limit 20 Deadband 1
High Limit Text: SupplyAirTempature too High. Low Limit Text: SupplyAirTempature too Low.
Limit Enable: enable lowLimitEnable and highLimitEnable. Save the changes.
展开OutOfRangeAlarmExt扩展属性 按下图修改其属性,并保存退出。
Honeywell ECC Asia Pacific Technical Assistance Center Page:47/130
5. Using Alarm Portal
Run “Alarm Portal” in Windows Stat menu Program. Run “Add Alarm Console” in Alarm menu.
运行开始菜单中“Alarm Portal”程序。 在Alarm菜单中选择“Add Alarm Console”添加报警控制台。
In the pop up window, input localhost as host address, Username and Password is same to when you create the station WEBs01.
在弹出窗口中,host 输入localhost表示本地计算机,用户名和秘密与建立工作站WEBs01时输入相同。
Next, and select a ConsoleRecipient. Finish.
Next按钮,选择一个ConsoleRecipient,Finish结束。
The Alarm Portal will automatic link to the alarm console and get the alarms. Alarm Portal 程序会自动连接到刚才设置的alarm控制台接收报警信息。
Honeywell ECC Asia Pacific Technical Assistance Center Page:48/130
Manually set SupplyAirTempature in AHUPoints to 32 degree. 在AHUPoints中人为设定SupplyAirTempature 32度。
After the set delay time, the alarm will appear with sound. You can acknowledge the alarm and click Hyperlink to the set page.
在设定的延时过后,报警页面会自动弹出并发出声音。你可以确认报警,并点击连接到设定的相关页面。
Honeywell ECC Asia Pacific Technical Assistance Center Page:49/130
6. HyperLink to Alarm Console 连接到报警控制台
Switch to the Px View of AHU01. Add a HyperLinkLable.
Modify property :Ord: station:|slot:/Services/AlarmService/ConsoleRecipient Text: “To Alarm Console” Test the Link.
切换到AHU01图形页面PxSheet。 添加一个HyperLinkLable。
修改属性 :Ord: station:|slot:/Services/AlarmService/ConsoleRecipient Text: “To Alarm Console” 测试连接。
Honeywell ECC Asia Pacific Technical Assistance Center Page:50/130
LAB 8 Schedule 时间表
Objective: How to use schedule module include weekly,calendar,trigger. 目标: 如何使用时间表模块,包括周,日历,触发等类型。
Instructions / 指导:
1. Add Weekly Schedule
添加周时间表
Open “Schedule” module in Palette. Place a “BooleanSchedule” on the Wire Sheet of AHU01Points.
Link “BooleanSchedule-Out” to “SupplyFanss-In16”
在Pallette中打开“Schedule”模块面板。放置一个“BooleanSchedule”到AHU01Points的Wire Sheet上。
连接“BooleanSchedule-Out”到“SupplyFanss-In16”。
Double click “BooleanSchedule”.
Set Weekly Schedule: 9AM~6PM Monday to Friday value true.
双击“BooleanSchedule”模块。
设置周计划 星期一到星期五9AM~6PM 值为true。
Honeywell ECC Asia Pacific Technical Assistance Center Page:51/130
On the Special Events tab, add a “Week and Day” type event: Every Monday of first Week every month. Value: PM12 to PM09 true.
在Special Events特殊实际面板,添加一个“Weed and Day”类型事件。每个月的第一个星期一,PM12到PM09值为true。
Honeywell ECC Asia Pacific Technical Assistance Center Page:52/130
Open “Schedule” module in Palette. Place a “NumericSchedule” on the Wire Sheet of AHU01Points.
Link “NumericSchedule -Out” to “ReturnAirSetpoint-In16”
在Pallette中打开“Schedule”模块面板。放置一个“NumericSchedule”到AHU01Points的Wire Sheet上。
连接“NumericSchedule-Out”到“ReturnAirSetpoint-In16”。
Double click “NumericSchedule”. Set Setpoint schedule as below: 双击“NumericSchedule”模块。设置设定点周计划如下图:
View the result in WireSheet. 在WireSheet中观察结果。
Honeywell ECC Asia Pacific Technical Assistance Center Page:53/130
2. Add Calendar Schedule module to Wire Sheet
添加日历时间表到Wire Sheet
Place a “CalendarSchedule” on the Wire Sheet of AHU01Points. Link “CalendarSchedule -Out” to “BooleanSchedule -In”
放置一个“CalendarSchedule”到AHU01Points的Wire Sheet上。 连接“CalendarSchedule -Out”到“BooleanSchedule -In”。
Double click CalendarSchedule, to modify the schedule and see the result in wire sheet.
双击CalendarSchedule,修改其时间计划,在wire sheet中观察结果。
3. Add Trigger Schedule module to Wire Sheet
添加触发时间表到Wire Sheet
Place a “TriggerSchedule” on the Wire Sheet of AHU01Points.
Double click “TriggerSchedule”, add a event: date-set tomorrow date and time-next 5minunts to now.
放置一个“TriggerSchedule”到AHU01Points的Wire Sheet上。
双击“TriggerSchedule”到“,添加一个事件,日期为下一日,时间为现在起的5分钟后。
Place a “BooleanWritable” and “Counter” into the wire sheet, Link as below. 添加一个“BooleanWritable” 和 “Counter”到wire sheet,如下连接。
Honeywell ECC Asia Pacific Technical Assistance Center Page:54/130
Manually active and inactive the “BooleanWritable” to count up value of Counter. Wait the minutes you have set, See the Out of Counter value change.
手动开关BooleanWritable点以增加Counter的计数值。 等到你设定的时间到达,观察Counter输出变化清零。
4. HyperLink to Schedule 连接到时间表
Switch to AHU01 PxSheet. Add a HyperLinkLable.
Modify property :Ord: station:|slot:/AHUPoints/BooleanSchedule Text: “To Schedule”
切换到AHU01图形页面PxSheet。添加一个HyperLinkLable。 修改属性 :Ord: station:|slot:/AHUPoints/BooleanSchedule Text: “To Schedule”
Honeywell ECC Asia Pacific Technical Assistance Center Page:55/130
LAB 9 History and Dynamic Trend 历史记录和动态趋势
Objective: How to HistoryService , history extension, manager the history and dynamic trend
目标: 如何使用历史记录服务,历史扩展属性,管理历史记录以及动态趋势。
Instructions / 指导:
History
1. Add History Service 添加History历史服务
Check whether the “HistoryService” is in the “Config\\Services”.
If not, open the “history” module in Palette. Select and drag the “HistoryService” in to the Services of Station(WEBs01).
检查报警服务 “HistoryService”是否在“Config\\Services”中。
如果没有,则打开Palette中的“history”模块。选择“HistoryService”并拖动到Station(WEBs01)的Services中。
2. Add History Extension to the Points 添加历史记录扩展到点
Open the Property Sheet for ReturnAirTempature in AHUPoints.
Add a NumericInterval history extension to the property of ReturnAirTempature.
打开AHUPoints中ReturnAirTempature的属性窗口。
添加一个NumericInterval类型的历史扩展到ReturnAirTempature的属性。
3. Modify the History Extension Property 修改历史记录扩展属性
Modify the History Extension property as below.
按如下所示修改该历史记录扩展属性。
Honeywell ECC Asia Pacific Technical Assistance Center Page:56/130
4. History Config 配置历史记录
Double click Services\\LogHistory\\History Config to open the property sheet. Configure the Capacity and and the Full Policy.
双击Services\\LogHistory\\History Config打开属性窗口。 配置历史记录容量和溢出策略。
5. View the History 查看历史记录
Double click “History” in Station(WEBs01) to the History Chart Builder.
Set Time Range, select the history points, type of chart, and click Build to view the result.
Honeywell ECC Asia Pacific Technical Assistance Center Page:57/130
双击Station(WEBs01)下的History进入History Chart Builder界面。
设置时间区间,选择要查看历史纪录的点,图表的类型,点击Build查看结果。
Right click on the chart and export. You can export to PDF or Excel file. 在图形上右键选择export导出。你可以输出到PDF或Excel文件。
Or you can directly double click the History extension point name in History/WEBs01 to view this point history.
In the View Selector, choose History Table to see the history in table format. Select the “Delta” to see the changes.
或者你可以直接双击History/WEBs01中历史记录点的名称查看这个点的历史记录。
Honeywell ECC Asia Pacific Technical Assistance Center Page:58/130
在ViewSelector中选择HistoryTable可按表格形式查看结果。选择”Delta”观察变化。
Double click the AuditHistory and LogHistory in History\\WEBs01 to view the result.
双击History\\WEBs01中的AuditHistory和LogHistory观察结果。
6. Manager the History 管理历史记录
Double click the HistoryService, all the History Extension will list in the History Ext Manager.
双击HistoryService,所有的历史纪录扩展会在History Ext Manager中显示。
Double click History in Station(WEBs01), in the View Selector choose Database Maintenance. Clear the records if you want.
双击Station(WEBs01)中History, 在View Selector中选择 Database Maintenance. 在这里可以清除不需要的记录。
Honeywell ECC Asia Pacific Technical Assistance Center Page:59/130
7. HyperLink to History 连接到历史纪录
Switch to AHU01 PxSheet. Add a HyperLinkLable. Modify property :
Ord: history:/WEBs01/ReturnAirTemperature (use History Chooser) Text: “To History”
切换到AHU01图形页面PxSheet。添加一个HyperLinkLable。
修改属性 :Ord: history:/WEBs01/ReturnAirTemperature (使用History Chooser) Text: “To History”
Honeywell ECC Asia Pacific Technical Assistance Center Page:60/130
Dynamic Trend
Open the PxSheet of AHU01. Drag and drop point “ReturnAirTempature” to the canvas of AHU01. In the popup windows, choose Time Plot.
打开AHU01的PxSheet。拖放点“ReturnAirTempature”到AHU01图形页面工作区。在弹出窗口中选择Time Plot.
Modify the size of this Time Plot widget. Switch to view mode to see the result. 修改Time Plot widget的大小。切换的查看模式观察结果。
Honeywell ECC Asia Pacific Technical Assistance Center Page:61/130
LAB 10 Report /Email 报表和邮件
Objective: Learn how to generate report, report format, and email service. 目标: 学习如何生成报表,报表格式,以及电子邮件服务。
Instructions / 指导:
Report Service:
1. Add Report Service 添加Report报表服务
Open the “Report” module in Palette. Select and drag the “ReportService” in to the Services of Station(WEBs01).
打开Palette中的“Report”模块。选择“Report Service”并拖动到Station(WEBs01)的Services中。
2. Layout report data in a ComponentGrid 设定报表格式
Add a “ComponentGrid”(from the Reporting palette) onto the desired location in
your nav tree (we put in ReportService now). Switch to Grid Editor view of “ComponentGrid”.
添加一个“ComponentGrid”(从Reporting palette)到nav tree上你想要的位置(我们放在ReportService中)。切换到“ComponentGrid”的 Grid Editor界面。
Drag and drop a point “SupplyAirTempature” to the Template row. 选中托拽点“SupplyAirTempature”到Template row 模板行。
Honeywell ECC Asia Pacific Technical Assistance Center Page:62/130
Drag and drop other points in AHU01Points to the Rows in Grid Editor. 将AHU01Points中其他的点,添加到Grid Editor 的Rows行中。
Drag and drop a point “SupplyAirTempature” to the columns. 选中并托拽点“SupplyAirTempature”到columns列。
Honeywell ECC Asia Pacific Technical Assistance Center Page:63/130
Drag and drop a point “SupplyAirTempature” to the columns, again. 再次添加点“SupplyAirTempature”到columns列。
Double click the second column, modify the name and format as below. 双击第二列名,按如下修改name名称和format格式。
Name: Value Format: %out.value%
Switch to Gird View to view the result. 切换到Gird View界面查看结果。
3. Create a Px page display of the report 为报表建立一个图形页面
Create a ReportPxFile in Files\\px of Station(WEBs01).
在Station(WEBs01) Files\\px 中建立一个ReportPxFile 文件。
Honeywell ECC Asia Pacific Technical Assistance Center Page:64/130
Create a folder “Report” in PxHome, and create a new view. In the Source choose the ReportPxFile.px just create, and choose Reuse in later popup window.
在PxHome中建立一个Report文件夹,并为期建立一个图形见面。在Source中选择刚才建立的ReportPxFile.px文件,在确认后的弹出窗口选择Reuse.
Add a “SectionHeader”(in report Palette) to the Report px page in edit view. 添加一个“SectionHeader”(在report Palette中)到Report的图形编辑界面。
Honeywell ECC Asia Pacific Technical Assistance Center Page:65/130
Drag and drop the “ComponentGrid” we have create onto the Report Px page under the “SectionHeader”. In the popup menu, choose Workbench View and Grid Table.
选中并拖放刚才建立的“ComponentGrid”到Report的图形界面放
在”SectionHeader”下。在弹出窗口中选择Workbench View和Grid Table.
Honeywell ECC Asia Pacific Technical Assistance Center Page:66/130
4. Create and configure ExportSource component
建立和配置ExportSource
Place a “ExportSource” (in the report palette) on the wiresheet of ReportService. Modify the property of “ExportSource” component. Trigger Mode: Manual
Source: choose the report folder in PxHome Exporter: select ReportPxFile/pdf.
拖放一个“ExportSource” (在report palette中)到ReportService的wiresheet中。 并按如下修改其属性。
Email Service
1. Add Email Service 添加Email服务
Open the “Email” module in Palette. Select and drag the “EmailService” in to the Services of Station(WEBs01). Enable the service in its property sheet.
打开Palette中的“Email”模块。选择“Email Service”并拖动到Station(WEBs01)的Services中。在其属性页面中使能这个服务。
Honeywell ECC Asia Pacific Technical Assistance Center Page:67/130
2. Add email account 添加email 帐户
Add a “OutgoingAccount” (in email Palette) to the EmailService Email Account Manager View. And configure the property as below. (hostname: smtp server IP)
添加一个“OutgoingAccount”发送帐户 (在email Palette中)到EmailService的Email Account Manager界面中。并按如下配置其属性。(hostname为smtp服务器IP)
3. Add EmailRecipient to ReportService
添加email接收器到报表服务
Add a “EmailRecipient”(from report palette) to the wiresheet of ReportService. Configure its property, input your email and choose the email account we just create. Link “ExportSource-out” to “Email Recipient-Route”.
Honeywell ECC Asia Pacific Technical Assistance Center Page:68/130
添加一个“EmailRecipient”( 在 report palette中)到ReportService的wiresheet中。配置其属性,输入你的email地址,并选择刚才建立的email account。 连接“ExportSource-out” 到 “Email Recipient-Route”.
Right click on ExportSource---Action---Generate, then check email for the report. 在ExportSource右键---Action---Generate,检查邮件是否收到报表。
4. Add EmailRecipient to AlarmService
添加email接收器到报警服务
Add a “EmailRecipient”( from email palette) to the wiresheet of AlarmService. Configure its property, input your email and choose the email account we just create. Link “DefauleAlarmClass-Alarm” to “Email Recipient-RouteAlarm”.
添加一个“EmailRecipient”( 在 report palette中)到ReportService的wiresheet中。配置其属性,输入你的email地址,并选择刚才建立的email account。 连接“DefauleAlarmClass-Alarm” 到 “Email Recipient-RouteAlarm”。
Honeywell ECC Asia Pacific Technical Assistance Center Page:69/130
Generate a alarm, then check email for the alarm report. 生成一个报警,检查邮件是否收到报警报表。
Honeywell ECC Asia Pacific Technical Assistance Center Page:70/130
LAB 11 Security 安全设定
Objective: Learn how to set security by configure Category and User service. 目标: 学习使用目录和用户服务来设定系统安全。
Instructions / 指导:
1. Configure CategoryService
配置CategoryService分类目录服务
Double click CategoryService in Config\\Services and go to the Category Manager view.
Create 3 new categories named: General; HVAC; Lighting.
双击Config\\Services里的CategoryService,进入Category Manager view界面。
创建3个新的category分类目录:General; HVAC; Lighting。
2. Assign Components to Categories 分配组件到分类目录
Open the Category Browser view. Assign all the components in the nav tree to Categories.
打开Category Browser视图。分别nav tree中所有的组件到分类目录中。
Honeywell ECC Asia Pacific Technical Assistance Center Page:71/130
3. Configure User Service 配置用户服务
Open the User Manager view by double click the UserService.
Add a new user named: Operator. Configure it properties as below:
双击UserService打开User Manager。
添加一个新的用户名为Operator。按如下配置其属性:
Honeywell ECC Asia Pacific Technical Assistance Center Page:72/130
Permissions 配置权限
Open the Permission Browser view of UserService to Manager permission for all users.
打开Permission Browser视图,管理所有用户的权限。
Honeywell ECC Asia Pacific Technical Assistance Center Page:73/130
LAB 12 Commissioning WEBs Controller
Objectives:
Get to know how initialize a WEBs controller. Including software modules installation, station copy, TCP/IP setting, Language and date time etc.
将了解如何初始化1个WEBs控制器,包括软件模块安装,Station复制,TCP/IP设定,语言及日期时间等。
Instruction:
1. Open the Platform of the remote WEBs controller. 打开远程WEBs控制器的Platform
2. Run Commission wizard
Right click the Platform. 运行Commission wizard, 右击图标
Honeywell ECC Asia Pacific Technical Assistance Center Page:74/130
3. Check the options that you would like to configure. 选择你想要设置的项。
4. Usually select UI+Runtime for module content filter level. 对于Module content filter Level配置,通常选择UI+Runtime
Honeywell ECC Asia Pacific Technical Assistance Center Page:75/130
5. Re-install the distribution files.
If necessary , re-install the core software from local PC to remote WEBs controller.如果必要,从本地PC重新安装核心软件到远程WEBs控制器。
The core software (Distribution file) is installed. 核心软件安装完毕。
Honeywell ECC Asia Pacific Technical Assistance Center Page:76/130
6. Install station from Local PC to the remote WEBs controller. 从本地PC安装station 到远程WEBs控制器
Select the necessary files that to be copied.
Honeywell ECC Asia Pacific Technical Assistance Center Page:77/130
选择复制必要的文件
7. Software modules installation.
Install the software modules from the Local PC. Before this you should assure that the needed software modules already in the “modules” folder of AX program directory in Local PC. For example, ”Honeywellspyder.jar” to be used in the remote WEBs controller that takes Spyder as Lon I/O for AHU control.
从本地PC安装软件模块。在这之前确认需要的模块已经在本地PC的AX的安装目录里的”modules”文件夹中。比如, 远程WEBs控制要将Spyder作为AHU控制的Lon I/O, 则需要复制”HoneywellSpyder.jar”.
Honeywell ECC Asia Pacific Technical Assistance Center Page:78/130
8. Configure the TCP/IP of the remote WEBs controller. 配置远程WEBs控制器的TCP/IP.
Honeywell ECC Asia Pacific Technical Assistance Center Page:79/130
9. Set the password and user name of the Platform of remote WEBs controller.
设定远程WEBs控制器的Platform的用户名和密码。
10 Install the Lexicon files to remote WEBs controller. 安装语言设置文件到远程的WEBs控制器。
Honeywell ECC Asia Pacific Technical Assistance Center Page:80/130
11. License files installation.
Usually, the WEBs controller has the license after shipped. You don’t need install the license file.
通常WEBs控制器在出厂后有License, 不需要安装License文件。
Honeywell ECC Asia Pacific Technical Assistance Center Page:81/130
12. Confirm the commission task list. 确认commission 任务列表。
Commissioning task completed. Commissioning 任务结束
Honeywell ECC Asia Pacific Technical Assistance Center Page:82/130
13. Open the station (WEBs01). 打开WEBs01 station.
Honeywell ECC Asia Pacific Technical Assistance Center Page:83/130
LAB 13 Use a Spyder as Lon I/O for WEBs.
Objectives:
In this lab, we try to add a Spyder controller as a Lon I/O. We will learn how to add a lonnetwork, add a device and configure I/Os of Spyder.
这个实验中,我们将尝试使用一个Spyder控制器作为Lon I/O.我们将学习如何添加Lonnetwork, 添加1个设备并且配置Spyder的I/O.
Instructions:
1. Add a Lon Network in the Driver Manager. 添加Lon NetWork
2. Confirm the installation of Spyder module.
Confirm that you have copied HoneywellSpyder.jar to WEBs ctroller in the last Lab. If not, you can do as following.
确认在上个实验中将”HoneywellSpyder.jar”复制到WEBs控制器,如果没有可以按下面的做。
Honeywell ECC Asia Pacific Technical Assistance Center Page:84/130
2.1. Copy the “HoneywellSpyder.jar” to the “Modules” folder of AX installation directory in Local PC.
将”HoneywellSpyder.jar” 复制到AX安装目录的”Modules”文件夹下。
2.2. Transfer the file to remote WEBs controller using File Transfer client of WEBs Platform.
使用WEBs 的Platform中的File transfer client 工具将HoneywellSpyder复制到WEBs的”Modules”文件夹下。
3 Add a Spyder.
Add a Spyder in Lon Device Manager that can be opened by double clicking the “LonNetwork”. Named it “IOFORAHU”.
双击打开Lon Devices Manager添加一个Lon Spyder 命名为”IOFORAHU”.
Honeywell ECC Asia Pacific Technical Assistance Center Page:85/130
4 Add the NVs for connecting DO of Spyder.
Initial Spyder has no nvi for directly control Spyder outputs from remote source. 添加用于连接Spyder的DO的NV变量。初始的Spyder没有提供远程直接控制Spyder输出的nvi变量。
4.1. open the NV Configuration View by clicking the popup menu.
通过点击弹出菜单打开NV Configuration View.
Honeywell ECC Asia Pacific Technical Assistance Center Page:86/130
4.2. Click “Add NV” to add two NVI for DO. 点击”Add NV” 添加2个用于DO的NVI。
Prosperities setting as following. 属性如下
Name NV type NV data type Others nviSFSS Network Variable Input SNVT_switch Default nviRFSS Network Variable Input SNVT_switch Default
Honeywell ECC Asia Pacific Technical Assistance Center Page:87/130
4.3 Select the “value” field of the new NV and click “Show on wiresheet as points”.
选择新的NV的”value” filed 并且点击”Show on wiresheet as points”
Honeywell ECC Asia Pacific Technical Assistance Center Page:88/130
5. Generate the NVs. 产生NV变量
5.1. Open “Controller Summary View” by double clicking the “IOFORAHU”, and select the right model number that matches the real Spyder.
双击”IOFORAHU”打开Control Summary View,选择和实际产品相同的型号。
5.2. Right click “IOFORAHU” and select Generate Nvs from the popup menu.
右击”IOFORAHU”并选择”Generate NVs”.
Honeywell ECC Asia Pacific Technical Assistance Center Page:89/130
6. Create the Lon proxy points for I/O control. 创建Lon代理点用于I/O控制
Double click the “points” of “IOFORAHU” to open the Lon Point Manager.
双击”IOFORAHU”的”Points”打开”Lon Point Manager”
Add the following points and set properties. 添加下列的点并设置属性
Name Type field NV ReturnAirTemperatNumric Point ui1 nvoIO1 ure
ReturnAirSetpoint Numric Point ui2 nvoIO1 SupplyFanStatus Boolean Point di1 nvoIO2 FilterDPS Boolean Point di2 nvoIO2 SupplyFanSS Boolean Writable do1 nviSFSS ReturnFanSS Boolean Writable do2 nviRFSS
7. Configure the UI signal type. 配置UI的信号类型
7.1. Open the “honeywellSpyder” palette for automatically setting device or object.
打开honeywellSpyder Palette用于自动的设备与对象设定。
Honeywell ECC Asia Pacific Technical Assistance Center Page:90/130
7.2. Double click the “ControlProgram” of “IOFORAHU” to open the wiring sheet, drag and drop the Moudlatinginput of UI setting. Name the new object “UI1”.
双击”ControlProgram”打开Wiring sheet,拖放Modulatinginput用于UI设定, 命名新的对象为UI1.
Honeywell ECC Asia Pacific Technical Assistance Center Page:91/130
7.3. Duplicate the UI1 for UI2 for same configuration. 因为设置相同复制UI1为UI2
8. Connect the NVIs to DOs.
Honeywell ECC Asia Pacific Technical Assistance Center Page:92/130
Connect the nviSFSS and nviRFSS to the DOs in wiring sheet of Control Program. Drag and drop the “Binary Output” to wiring sheet and name it “DO1”. then duplicate the DO1 for DO2.
在wiring sheet 连接nviSFSS和nviRFSS 到DO上。拖放 Binary Output 到Wiring sheet 上并且命名为DO1,再复制DO1为DO2.
Link the nviSFSS_value to DO1, nviRFSS_value to DO2. 连接nviSFSS_value到DO1,nviRFSS_value到DO2.
Honeywell ECC Asia Pacific Technical Assistance Center Page:93/130
9.Commission the Spyder.
Commission the Spyder in Lon Device Manager.Click Service Pin if don’t know the Neuron ID, otherwise you can fill the neuron ID directly.
在Lon Device Manager里Commission这个Spyder. 如果不知道Neuron ID,可以点击Service Pin, 否则你可直接输入Neuron ID。
10 Download
Download the control program to Spyder that keeps the UI and DO configuration for effective.
下载保存着UI和DO配置的 Control program到Spyder控制器。
Honeywell ECC Asia Pacific Technical Assistance Center Page:94/130
11.View the result of I/O. 观察I/O值
11.1. Open the Lon Point Manager of Points to see the result of Lon Proxy points. 打开Lon Point Manager 观察Lon代理点的值。
Honeywell ECC Asia Pacific Technical Assistance Center Page:95/130
11.2. Connect the proxy points to the control points that created in pervious Labs to check the connectivity. Or directly link with the program and graphics.
(Duplicated points occupy double resources, less proxy points and control points is recommended)
连接代理点到先前试验中建立的控制点来检查连通性。或者直接连接到先前的程序和图形中。(重复的点占用双重的资源,建议用尽量少的代理点和控制点)
AHUPoints IOFORAHU\\Points Demo board
ReturnAirTemperature Å ReturnAirTemperature Å Potentiometer 1# ReturnAirSetpoint Å ReturnAirSetpoint Å Potentiometer 2# SupplyFanStatus Å SupplyFanStatus Å Switch 1# FilterDPS Å FilterDPS Å Switch 2# SupplyFanSS Æ SupplyFanSS Æ LED 1# ReturnFanSS Æ ReturnFanSS Æ LED 2#
Turn round the potentiometers on the Demo board, observe the result of the points, ReturnAirTemperature, ReturnAirSetpoint, CoolingValve, HeatingValve. Turn on/off the switches on the Demo board, to see if the LED on/of properly.
旋转实验板上的电位计,观察点的结果。切换板上的开关,看看LED灯是否正确开关。
Honeywell ECC Asia Pacific Technical Assistance Center Page:96/130
Honeywell ECC Asia Pacific Technical Assistance Center Page:97/130
LAB 14 Link Station to Station
Objectives:
We try to connect the remote WEBs controller to Local PC by linking stations.我们通过连接station来连接本地PC和远程的WEBs控制器。
Instruction:
1. Open the stations.
Open the platform and “WEBs01” station of local PC that built in the pervious Labs. Open the platform and “WEBs02” station of remote WEBs controller that built in the last Lab.
打开本地PC的platform和之前实验里建立的”WEBs01” station。打开远程WEBs控制器的platform和上个实验建立的”WEBs02”Station.
2. Add Negara network in the Local PC.
Add a Niagara Network in the Driver manager of “WEBs01” by clicking “Drivers”.
在WEBs01的Drivers中添加Niagara Network.
Honeywell ECC Asia Pacific Technical Assistance Center Page:98/130
Important in Lab: if there are duplicated names for station that running on different PCs or WEBs controller in a net, you won’t find all the stations. Rename the station or segment the Lan.
在实验中如果存在station重名的话,将不会找到重名的station.可以重命名或者给网分段。
3. Add a new remote station in Local PC
Add a new remote station in the Station Manager of Niagara Network. (Also, you can Discover the online stations on TCP/IP connection) 添加新的远程station.
Honeywell ECC Asia Pacific Technical Assistance Center Page:99/130
4. Configure the properties of remote station.
Configure the properties of this new remote station that should be coordinated with the WEBs02 on the remote controller.
配置station的属性必须和远程控制器上的WEBs02一致。
5. Create the Niagara proxy points.
5.1 Discover the points of the remote station that can be connected to program or graphics on Local PC. Double click the “Points” to open “Niagara Point Manager”
, click “Discover” to show up a Query builder, Search depending on certain match conditions that you can define.
查询远程Station上的点,这些点可以连接到本地PC上的程序和图形。双击”Points”打开”Niagara Point Manager”, 点击”Discover” 呈现查询窗口,你可定义匹配条件进行搜索。
Honeywell ECC Asia Pacific Technical Assistance Center Page:100/130
5.2 Select the points that Local PC will monitor. 添加本地PC要监视的点。
Tips: you can select the items by pressing “Ctrl” or “Shift” key to operate in batch.
提示:可使用”Ctrl”或”Shift” 键进行选取。
Honeywell ECC Asia Pacific Technical Assistance Center Page:101/130
5.3 Add the following points that will read the status and value from remote WEBs.
添加以下的要从远程WEBs上读取状态和数值的点。
6. Link the Niagara proxy points to the control points.
Link the control points in the Local PC and the proxy points that discovered in the last step. We also can link the remote points to the program or graphics directly in the Local PC. (Actually, in real jobs, we use control points or proxy points as few as possible for saving resources.) You are attention that all the remote points are read only for the Local PC whatever type the remote points are.
连接本地PC上的控制点和上步找到的代理点。我们也可以直接将这些远程点直接连接到本地PC上的程序或图形上。(实际上,我们尽量少采用控制点和代理点来节省资源)。注意所有的远程点对于本地PC来讲是只读的,不论远程的点实际是否可写。
WEBs01\\Config\\AHUPoints
WEBs01\\Config\\Drivers\\NiagraraNetwork\\WEBs02\\Points
ReturnAirTemperature Å ReturnAirTemperature ReturnAirSetpoint Å ReturnAirSetpoint SupplyFanStatus Å SupplyFanStatus FilterDPS Å FilterDPS
7. Configure the Firewall of Local PC.
7.1Change the Firewall configuration of Local PC for being visited from other AX Station (of WEBs controller or PC) and IE users. Open the Window Firewall of XP. Keep the Firewall “On” for security. Then open Exception on option bar.
为了其他AX Station和IE用户访问,需要修改防火墙设置。打开Window Firewall,保持防火墙打开,打开Exceptions.
Honeywell ECC Asia Pacific Technical Assistance Center Page:102/130
7.2 Add ports for Exceptions. 添加例外端口。
Add following common ports that AX uses. These ports also are according to the TCP/IP setting of platform and stations.
添加AX通常使用的端口,这些端口要和platform和Station的TCP/IP设定一致。 AXStationPort1, 1911 Station can be connected in other AX station. AXPlatform, 3011 Platform can be connected in other AX Station. AXIEUser 80 User can browser the AX station in other PC.
Honeywell ECC Asia Pacific Technical Assistance Center Page:103/130
8. Add Niagara network in remote WEBs controller.
Open the Driver Manager of “WEBs02” in the remote controller. Add new Niagara Network and station “WEBs01” same setting with the Local PC.
打开远程控制器上的WEBs02的Driver Manager.添加新的Niagara Network和WEBs01 station 和本地PC相同设置。
9. Create the Niagara proxy points on remote WEBs controller.
Discover and add the points from WEBs01. Add the following points that will send command from Local PC to remote WEBs controller.
查找和添加WEBs01上的点,添加以下将会从本地PC发送指令到远程WEBs控制器的点。
Honeywell ECC Asia Pacific Technical Assistance Center Page:104/130
9. Let Local PC control Spyder I/O.
Delete the “AHUPoints” under “WEBs02\\Config”.This action will also delete the links that we made in Lab13. Now we will let the program and graphics in Local PC control the Spyder outputs. So link the points added in the last step to the Lon Proxy Points for Spyder I/O.
删除”WEBs02\\Config”下的”AHUPoints”.此操作也将删除我们在Lab13建立的连接。现在我们要本地PC上的程序和图形来控制Spyder的输出。所以连接上一部建立的点到Spyder的Lon代理点。
WEBs02\\Config\\Driver\\LonNetwork\\IOFORAHU WEBs02\\Config\\Drivers\\NiagraraNetwork\\WEBs01\\Points SupplyFanSS Å SupplyFanSS ReturnFanSS Å ReturnFanSS
10. Test Connectivity.
Open the IE page for WEBs01 station on Local PC. Change the potentiometers and switches on Demo board, and check the connectivity to program and graphics.
打开WEBs01的IE页面。改变实验板上的电位计和开关,检查程序和图形的连通性。
Honeywell ECC Asia Pacific Technical Assistance Center Page:105/130
LAB 15 Module Library and Reuse 模块库和重复利用
Objective: Import new module library, reuse program/graphics, customize a palette. 目标: 导入新的模块,重复利用程序和图形,自定义palette。
Instructions / 指导:
1. Import new modules 导入新的模块
Copy file “honeywellspyder.jar” to “Niagara Workbench install folder\\modules”. 复制文件“honeywellspyder.jar”到“Niagara Workbench 安装目录\\modules”。
Open Palette, find and open honeywellspyder modules. 打开Palette, 找到并打开honeywellspyder模块。
2. Customize a palette 自定义palette
Create a new “PaletteFile.palette” in Files system of Station(WEBs01).
在Station(WEBs01)的Files文件系统下新建一个PaletteFile.palette文件。
Open the WireSheet of the PaletteFile.
Open “kitpx” in Palette, drag and drop “BoundLabel” to the wiresheet.
Open “kitControl” in Palette, drag and drop “HVAC” folder to the wiresheet.
Honeywell ECC Asia Pacific Technical Assistance Center Page:106/130
打开PaletteFile的WireSheet。
打开”kitpx”Palette”, 拖放”BoundLabel”到wiresheet. 打开”kitControl”,拖放”HVAC”文件夹到wiresheet.
Press Save Bog in the tool bar to save. 按工具栏中Save Bog按钮保存。
Open Palette and browse and open the “PaletteFile.palette” in file system. Then
you can use the customized palette.
打开Palette,浏览并在文件系统中打开”PaletteFile.paltte”。这样就可以使用自定义的palette了。
3. Reuse Program 重复利用程序
Method 1: Right click on AHULogic, and select Duplicate or Copy and Paste.
方法1:在AHULogic上右键,选择”Duplicate”或复制与粘贴。
Method 2: Add the AHULogic folder to customize palette. Drag and drop from palette to when you need reuse it.
Honeywell ECC Asia Pacific Technical Assistance Center Page:107/130
方法2:添加AHULogic文件夹到自定义palette。在需要重复利用时从palette拖放。
4. Reuse Graphic 重复利用图形
Method 1: Right click on PxHome\\AHU01, and select Duplicate or Copy and Paste.
方法1:在PxHome\\AHU01上右键,选择”Duplicate”或Copy与粘贴。
Method 2: Add the PxHome\\AHU01 folder to customize palette. Drag and drop from palette to when you need reuse it.
方法2:添加PxHome\\AHU01文件夹到自定义palette。在需要重复利用是从palette拖放。
Honeywell ECC Asia Pacific Technical Assistance Center Page:108/130
LAB 16 Backup 备份
Objective: Backup and restore the station, Histories Archive 目标: 备份和恢复工作站,历史记录归档
Instructions / 指导:
1. Back up the Station 备份工作站
Double click the BackupService in Services, then open the property sheet of
BackupService. Set exclude files and directories. (You can use default settings at this time.)
双击BackupService,打开其属性页面。设置不需备份的文件和文件夹。
Open the view of Backup Manager.
Click the Backup button, and set the destination for the backup file. The default folder is “Niagara Workbench installation folder\\backups”. Click the Save button to execute the backup.
打开Backup Manager视图。
Honeywell ECC Asia Pacific Technical Assistance Center Page:109/130
点击Backup按钮,并设定备份的目标文件。默认路径为NiagaraWorkbench安装目录\\backups。
点击Save按钮执行备份。
2. Restore the Station还原工作站备份
Double click the “Distribution File Installer” in Platform of Station(WEBs01).
双击Station(WEBs01) Platfrom中“Distribution File Installer”。
Change Directory to where you put backup files. All the backup files will be listed in the window.
改变目录路径到你存放备份文件处。所有的备份文件会在窗口中列出。
Honeywell ECC Asia Pacific Technical Assistance Center Page:110/130
Select the backup file you want to restore and click Install button.
选择需要恢复的备份文件,按Install 按钮。
Honeywell ECC Asia Pacific Technical Assistance Center Page:111/130
After installing success. The station has been backup into the controller.
在安装完成后。备份文件的站点被恢复到控制器中。
3. Histories Archive 历史记录归档
History Import 历史导入
o Double click “NiagaraNetwork” in Station(WEBs01)\\Config\\Drivers
双击Station(WEBs01)\\Config\\Drivers中的“NiagaraNetwork”。
o Expand WEBs02 and double click Histories in it, open the view of “Niagara History Import Manager”.
展开WEBs02并双击其中Histories, 打开“Niagara History Import Manager”视图。
o Click “Discover” button, all the history points in the remote station WEBs02 will show out in the Discovered window.
点击“Discover”按钮,所有在远程站点WEBs02中的历史记录点会在窗口中显示。
Honeywell ECC Asia Pacific Technical Assistance Center Page:112/130
o Double click on the history point you want to import, and configure the properties in popup window.
双击你需要导入的历史纪录点,并在弹出窗口中配置属性。
o Run the Archive manually. 手动运行Archive。
Honeywell ECC Asia Pacific Technical Assistance Center Page:113/130
o In the tree of Station(WEBs01)\\History the history import from Remote station WEBs02 will show out.
在树形目录Station(WEBs01)\\History中从远程站WEBs02中导入的历史记录会出现。
Before manually archive After manually archive
运行Archive前 运行Archive后
• History Export 历史记录导出
o Double click “NiagaraNetwork” in Station(WEBs01)\\Config\\Drivers
双击Station(WEBs01)\\Config\\Drivers中“NiagaraNetwork”。
o Expand WEBs02 and double click Histories in it. Open the view of “Niagara History Export Manager”.
展开Expand WEBs02,双击其中Histories。打开“Niagara History Export Manager”.视图。
o Click “Discover” button, all the history in local station WEBs01 will show out. in the Discovered window.
点击”Discover”按钮,所有本地站点WEBs01的历史记录将会出现在窗口中。
Honeywell ECC Asia Pacific Technical Assistance Center Page:114/130
o Double click on the history point you want to export to remote station, and configure the properties in the popup window.
双击你想要导出到远程站点的历史记录点,并在弹出窗口中配置其属性。
o Run the Archive manually. 手动Archive归档。
Honeywell ECC Asia Pacific Technical Assistance Center Page:115/130
o In the tree History of remote Station(WEBs02), the history export from station WEBs01 to WEBs02 will show out.
在远程站点WEBs02的树形目录中的History,从WEBs01导出到WEBs02的历史记录会显示。
Before manually archive After manually archive 手动归档前 手动归档后
Honeywell ECC Asia Pacific Technical Assistance Center Page:116/130
LAB 17 Spyder Commissioning
Objectives:
In this Lab, we will configure, program and commission a Spyder for a simple VAV application. Including connecting a T7560, Flow control, Flow calibration, application reuse.
这个实验里我们要用Spyder作为一个简单VAV应用进行配置编程和调试.包括连接一个T7560, 流量控制, 流量矫正,程序复用等。
Instruction:
1. Install HoneywellSpyder module into WEBs controller.
Connect the remote WEBs controller, and install “HoneywellSpyder.jar” into the controller with File Transfer Client, but first copy these file into “Modules” folder of AX installation directory of Local PC first.
连接远程的WEBs控制器,用File Transfer Client安装”HoneywellSpyder.jar” 到控制器上。之前要先将这些文件拷贝到AX安装路径”Modules”文件夹下。
2. Add Spyder.
Add a Spyder in Lon Device Manager, name it “VAV01”.
在Lon Device Manager里添加1个Spyder,命名为VAV01.
3. Define the model number.
Define the model number in “Controller Summary View” that according with “PVL” for VAV application.
定义Controller Summary View 里的型号。
4. Define the application type of ControlProgram . Select “VAV application” in Detail view of ControlProgram.
定义ControlProgram的Detail里为VAV application.
5. Use T7560 as the wall module.
Before program for T7560, we should confirm the wiring and specification.
Honeywell ECC Asia Pacific Technical Assistance Center Page:117/130
在编程前,确认T7560的连线和规格。
5.1. Do wiring between T7560 and PVL
T7560 PVL6438N(PVL6436) Sensor (2) ÅÆ UI1 Setpoint (3) ÅÆ UI2 Override button (5) ÅÆ DI1 LED(6) ÅÆ AO3 24VAC/DC(8) ÅÆ 20VDC Com (1) ÅÆ Com
5.2. Setting up the T7560 (refer to the T7560 installation manual) Setpoint type: P1:4 Centigrade absolute Room Temperature: P2:2 Display room temperature Bargraph use: P3:1 No Fan
Occupancy mode display: P4:6 Excel 500 signaling from controller Signal volt on Graphic Occupancy Mode Override mode LED (if Bypass or not )
Occupied OccNull or Bypass 10V 8V 6V 0V Unoccupied Bypass Unoccupied OccNull or Unoccupied Other modes OccNull
5.3. Write down the room sensor type and setpoint specification of T7560.
记录T7560的房间传感器类型和设定的规格
Room sensor: NTC20K
Setpoint: 12C ÅÆ9958.0Ohm; 30CÅÆ1150.0Ohm
6. Program for T7560 and Occupancy calculation.
6.1. Drag and drop “Application” of “Util” from Spyder palette in to “Control program”
拖放一个Application 到Control program.
Honeywell ECC Asia Pacific Technical Assistance Center Page:118/130
We will put programs about the wall module and occupancy mode calculation into this “Application”.
我们将在这个Application里放置墙面模块以及占用模式计算的程序
6.2 Open wiring sheet of “T7560” by double clicking the icon. Drag and drop the physical input/outputs into the wiring sheet. And assign the terminal to the relative I/O in “Terminal Assignment View” of “VAV01”.
通过双击T7560的图标打开wiring sheet. 拖放以下的physical input/output 到wiring sheet. 并且在VAV01的Terminal Assignment View里安排相关的I/O端子。
Name Type Setting Terminal OVD Binary input Keep defaults. DI1 LED Physical Keep defaults. AO3 output
OVD: Override button on T7560.
6.3. Build up the sequence for Occupancy and wall module inputs and outputs.
Honeywell ECC Asia Pacific Technical Assistance Center Page:119/130
Drag and drop the following modules from Spyder palette and setting the properties.
建立占用模式及墙面模块的输入输出。拖放以下的模块并且配置属性。
Name Module Source Properties Wall module Wall module Builtin Bypass time: 60min Schedule Schedule Builtin Keep defaults OccupancyArbitrator OccupancyArbitratorZoneArbitrationKeep defaults LEDCov Select Analog Default: Constant, 0.0,
Yes
Input0: Constant, 100.0,Yes
Input1: Constant, 60.0, Yes
Input2: Constant, 80.0, Yes
Input3: Connector, No
Input4: Connector, No
Input5: Connector, No
6.4. Link the modules and input/output points.
连接模块和输入输出点
Links Link from Link to
Link0OVD\\Out Wallmodule\\Override 1
Link0Wallmodule\\WM_Override OccupancyArbitrator\\WMOverride 2
Link0Schedule\\Current_State OccupancyArbitrator\\scheduleCurr3 entState Link0OccupancyArbitrator\\Eff_OCC_CurreLEDCov\\x 4 nt_State
Link0LEDCov\\Output LED\\in 5 6.5. Reorder the modules execution order.
按下面的执行顺序Reorder.
Honeywell ECC Asia Pacific Technical Assistance Center Page:120/130
OccupancyArbitrator : 1, LEDCov: 2.
7. Test the wall module and occupancy sequence.
7.1. Commission the Spyder controller and download.
Commission Spyder 控制器并且Download.
7.2. Debug the program (Spyder will change to online debug mode automatically)
Click to add the debug point, only add the points you can diagnosis them online.
Otherwise, the value of points is not proper.
Press the bypass button of wall module to check the bypass mode display.
添加调试点,这些点是你要进行在线调试的点,否则这些点的显示并不正确。按墙面模块上的Bypass键来验证Bypass模式是否显示正确。
Holding time Display Holding for 1.2~4 seconds or
Holding for 4.1~7 seconds Honeywell ECC Asia Pacific Technical Assistance Center Page:121/130
Holding for 7.1 seconds above or
8. Program for VAV flow control.
Before this step, we should assume a simple VAV application.
在这个步骤前, 我们假设一个简单的VAV程序
• Single duct, no reheat, cooling mode although year. 单风道,无再热全年制冷。
• Pressure independent, flow control. 压力无关,流量控制。
• In Unoccupied mode, damper keeps position for the minimum flow. 在非占用模式下,风阀保持最小流量开度。
8.1. Add “Application” from Spyder palette and name it “Flowcontrol”. Drag and drop the following physical inputs/outputs into the wiring sheet of “Flowcontrol”.
添加一个”Application” 并且命名为”Flowcontrol”,拖放以下的physical inputs/outputs到wiring sheet里。
Name Type Setting Terminal RMT Physical input NTC20K, Celsius UI1 SPT Physical input Custom resistive, Temperature, UI2
Celsius,
Input Low: 1150.0, Output Low: 30C
Input High: 9958.0, Output High: 12C
Flowsensor Physical input Type: On_Board_Pressure UI0(Fixed) Unit: Pascal
Floatdamper Physical Type: Acutator DO7 output Travel time:90s DO8
AutoSyncType: Sync Closed AutoSyncIntervel: 24hrs
PowerSyncType: Sync Closed Others: Keep defaults.
8.2. Add the following modules with same execution order and setting the properties.
Honeywell ECC Asia Pacific Technical Assistance Center Page:122/130
按照以下的执行顺序添加模块并且设定属性。
Name Module Source Properties FlowVelocity FlowVelocity Math Kfactor: 0.123 (just for sample) Others: Keep defaults
PIDEnable Select Analog Default: Constant, 1.0, Yes Input0: Constant, 0.0, Yes Input1: Connector, No Input2: Constant, 0.0, Yes Input3: Connector, No Input4: Connector, No Input5: Connector, No
CoolPID Pid Control Tr: 5C Other: keep defaults
Flowcontrol Flowcontrol Control minFlowSetPt: 20 (just for samples)
maxFlowSetPt:100 (just for samples)
Others: Keep defaults.
8.3. Link the modules and input/outputs as following table.
连接模块和输入输出。
Links Link from Link to Link0RMT\\Out CoolPID\\sensor 6
Link0SPT\\Out CoolPID\\setPt 7
Link0T7560\\OccupancyAbitrator\\Eff_Occ_Current_PIDEnable\\x 8 State
Link0PIDEnable\\Output CoolPID\\disable 9
Link1CoolPID\\Output FlowControl\\cmdFlowperc0 ent
Link1Flowsensor\\Out FlowVelocity\\press 1
Link1FlowVelocity\\FLOW FlowControl\\sensoredFlow2 Vol
Link1FlowControl\\Damper_pos FlowDamper\\in 3 Honeywell ECC Asia Pacific Technical Assistance Center Page:123/130
8.4. Download and test the flowcontrol program. 下载并且测试flowcontrol程序 Add the the outputs of RMT, SPT,Flowsensor FlowVelocity, CoolPID, Flowcontol to the diagnosis points lists for online debug.
添加RMT,SPT,Flowsensor,FlowVelocity,CooPID,Flowcontrol的Output用于调试。
• To see if the damper is opened more when sensor high than setpoint. 看看在温度高于设定值时风阀是否打开更大。
• To see if the damper is closed more when except Occupied and Bypass
mode.
看看除了Occupied 和Bypass模式外是否风阀是否关闭更小。
Honeywell ECC Asia Pacific Technical Assistance Center Page:124/130
9. Calibrate the sensors
First you should open the “Controlprogram”.
Right click the Spyder, and click on the popup menu.
首先打开Controlprogram,右击Spyder, 点击弹出菜单上的选项。
10. Diagnose Outputs
First, you should open the “ControlProgram”.
Click on “Diagnose outputs” for this operation. Directly change the Edit value to test the wiring and the reliability of outputs devices.
首先要打开ControlProgram, 选择”Diagnose Output”, 更改Edit Value来测试接线和输出设备。
You can change the Edit Value for calibration.
你可更改Edit Value来矫正。
Honeywell ECC Asia Pacific Technical Assistance Center Page:125/130
11. Calibrate the flow simply.
11.1. Use Diagnose Output tool to force Damper fully open (100%), and close the dialog window with keep Spyder in manual mode.
适用Diagnose Output工具强制风阀100%开,关闭对话框但是保持Spyder在manual模式下。
11.2. Get the actual flow when damper in fully opened (maximum flow), and get the K factor of the VAVBox, do the calculating.
在风阀100%开启的情况下,获取VAVBox的K参数,做以下计算。
Honeywell ECC Asia Pacific Technical Assistance Center Page:126/130
Actual DP= (Flow/K)2 Flow – M3/h DP— Pa Units depend on the definition of the manufactory of VAVbox.
单位取决于VAVBox厂商的定义。
11.3. Calibrate the flow sensor. Fill in the Actual DP and write up the offset value. (Note: when Spyder is reset, power down/up or download program the offset value will be clear to zero).
矫正流量传感器。填入Actual DP 并且记录offset 值。注意:当Spyder 被Reset, 电源关开或者下载程序这个offset值会清零。
11.4. Enter the Diagnostic Output window, change the manual mode to auto mode for normal running.
进入Diagnostic Output窗口, 更改manual模式到auto模式使Spyder进入正常运行。
Honeywell ECC Asia Pacific Technical Assistance Center Page:127/130
12. Use Spyder library.
In this section we try to backup our programs that we made in pervious steps. And import some Spyder library for reference.
这个部分我们尝试备份我们在之前的步骤中建立的程序,并且输入一些供参考的Spyder Libraryl
12.1. open the Spyder library 打开Spder library.
12.2. Create a new Application for reuse. Name it “VAV”
建一个新的Application,命名为VAV
Honeywell ECC Asia Pacific Technical Assistance Center Page:128/130
12.3. Drag & drop the Applications of VAV01 to the new “VAV” application. Add save library.
拖放VAV01中的Application到这个新的VAV application.并保存library.
12.4. Import the App_Lib_Rel to the Spyder Library
Unzip the App_Lib_Rel.zip to a folder, then use Import tool to browser this folder. Select the jar file you want to reuse.
解压App_Lib_Rel.zip到一个文件加。适用Import 工具浏览这个文件夹,选择你想要复用的Jar文件。
Honeywell ECC Asia Pacific Technical Assistance Center Page:129/130
12.5. Load the imported or saved applications (devices) for reuse.
Add a new Spyder controller, drag and drop the application to Spyder Controlprogram. You may do some changes.
添加一个新的Spyder 控制器,拖放程序到新的Spyder 的Control Program. 你也许要做一些更改。
Honeywell ECC Asia Pacific Technical Assistance Center Page:130/130